Features
Abort switches provide a manual Fire Suppression
System release abort request:
Pushbutton momentary switch is mounted on a
stainless steel single-gang plate
A protruding collar protects the switch from
accidental contact (collar is removable if required)
Available flush or surface mount
Flush mounting requires standard single-gang box
Surface mounting includes a red mounting box
Models are available with internal 1.2 k resistor for
current limited operation
Maintenance switches provide a secure and visible
disconnect means for servicing Fire Suppression
System Releasing Appliance Circuits (RACs):
Maintained position keyswitch with key removable
only in the normal position
Disabled position opens connection to output circuit
and places a 16.2 k
resistor across the input circuit
to initiate a supervisory condition at the host panel
Models with indicator lamp use a bright incandescent
bulb with red lens, powered from separate 24 VDC
Available for flush or surface mount
Flush mounting requires a standard double-gang box
for models with lamp or a standard single gang box
for models without lamp.
Surface mount models includes a red mounting box
Models with lamp provided with a double gang
stainless steel plate. Models without lamp provided
with a single gang stainless steel plate.
UL listed to Standard 864
Description
Releasing systems require maintenance disconnect switches
and often require abort switches. These abort and
maintenance switches are clearly labeled and combine easy
operation with rugged construction for high integrity
operation.
NORMAL
DISC./
DISABLE
FIRE SUPPRESSION
DISCONNECT / DISABLE
0
1
Maintenance Switches, with and without Disconnect
Indicator Lamp
PUSH AND HOLD
FIRE SUPPRESSION
SYSTEM ABORT
Abort Switch
* Refer to page 2 for specific product listings. NOTE: MEA is not applicable to
Maintenance Switches. FM
is not applicable to Abort Switches.
As indicated on page 2, these products have been approved by the California State Fire
Marshal (CSFM) pursuant to Section 13144.1 of the California Health and Safety Code. See
CSFM Listing 7300-0026:313 for allowable values and/or conditions concerning material
presented in this document. Abort switches are accepted for use – City of New York
Department of Buildings – MEA35-93E. Maintenance switches were not approved by FM as
of document revision date. Additional listings may be applicable, contact your local Simplex®
product supplier for the latest status. Listings and approvals under Simplex Time Recorder
Co. are the property of Tyco Fire Protection Products.
Releasing System Peripherals
UL, ULC, CSFM Listed;
Fire Suppression System Abort Switches and Releasing
MEA (NYC) Acceptance*
Appliance Circuit (RAC) Maintenance Switches
S2080-0010-5 3/2017
2
S2080-0010-5 3/2017
Abort Switches
Model
Description
Listing Status
Details
2080-9056 Flush mount
UL & CSFM listed;
MEA (NYC)
Acceptance
Single-gang size; includes 3 position contact block housing
with one contact block installed
2080-9057
Surface mount; includes
red mounting box
Abort Switches for 4004R Series Suppression Release Panel Current Limited Operation
Model
Description
Listing Status
Details
2080-9067 Flush mount
UL & CSFM listed;
MEA (NYC)
Acceptance
Single-gang size; includes 1.2 k
, 1W resistor for current
limited operation and 3 position contact block housing with
one contact block installed.
2080-9068
Surface mount; includes
red mounting box
Note: For ULC listed abort switches, refer to datasheet S2080-0011.
Maintenance Switches with Disconnect Indicator Lamp
Model
Description
Listing Status
Details
2080-9059 Flush mount
UL, ULC, & CSFM
listed
Double-gang size; includes 3 position contact block housing
with 2 contact blocks installed; disabled position opens
connection to output and places a 16.2 k
resistor across the
input circuit; resistor is removable if required for retrofit
2080-9060
Surface mount; includes
red mounting box
Maintenance Switches without Disconnect Indicator Lamp
Model
Description
Listing Status
Details
2080-9069 Flush mount
UL, ULC, CSFM
listed;
Single-gang size; includes 3 position contact block housing
with 1 contact block installed; disabled position opens
connection to output and places a 16.2 k
resistor across the
input circuit; resistor is removable if required for retrofit
2080-9070
Surface mount; includes
red mounting box
Accessories for Field Installation
Model
Description
2080-9061
Additional Contact Block for Abort or Maintenance Switch; 1 Form C contact; UL recognized component for use
with these switches; listings and approvals are not applicable
Abort Switch Installation Reference
Product Selection
(see page 3 for specifications)
Electrical Ratings
Abort Switch; One Contact block
Silver contacts; 1 N.O. & 1 N.C.; rated 2 A resistive @ 30 VDC
Maintenance Switch Control
Contact Block (all models)
Circuit control: Silver contacts; 1 normally open & 1 normally closed; rated 2 A resistive
@ 30 VDC
Maintenance Switch Lamp
Contact Block; (models 2080-
9059 and 2080-9060)
Lamp control: Silver contacts; 1 normally open & 1 normally closed; rated 2 A resistive
@ 30 VDC
Maintenance Switch Indicator
Light (models 2080-9059 and
2080-9060)
Replaceable 2 W incandescent bulb; 24 to 30 VDC typical; 83 mA @ 24 VDC; requires
separate 24 VDC
Wiring Connections
Abort Switch
Terminal blocks for in/out wiring; 18 to 14 AWG wire (0.82 mm
2
to 2.08 mm
2
)
Abort Switch with Current Limited
Resistor
Terminal blocks for first wire connection; 18 to 14 AWG wire (0.82 mm
2
to 2.08 mm
2
);
18 AWG wire lead for second wire connection
Maintenance Switch
18 AWG (0.82 mm
2
) color coded wire leads for suppression circuit; terminal blocks for
lamp wiring; 18 to 14 AWG wire (0.82 mm
2
to 2.08 mm
2
)
Additional Information
579-416, Installation Instructions
Environmental Ratings
Temperature Range
32° F to 120° F (0° C to 49° C)
Humidity Range
Up to 93% at 90°F (32° C)
Tyco Fire Protection Products • Westminster, MA • 01441-0001 • USA